Are there air filters specifically for smoke removal?

Jason Peng, an engineer at Deiiang Company

  • Author:Jason Peng

  • Cleanroom Engineering Technology Manager of Deiiang Company.

    Product R&D Manager of GDC Inc. Cleanroom Equipment Manufacturing Company.

    Executive Director of Guangdong Cleanroom Industry Association of China.

  • 2025-01-02  |  Visits:
Yes. air filters can be made to serve the purpose of smoke removal, but in order to eliminate smoke efficiently, the filters need to be arranged in three distinct stages which comprise an air pre-filter, a high-efficiency particle air filter, and a media stage incorporating activated carbon or other forms of chemical treatment. Hence it is clear to see that there is no single filter available for the effective removal of smoke haze and smoke odors; instead it is imperative to specify a smoke removal air filter as a complete system rather than relying solely on a different component of the smoke air filter.

Smoke is probably one of the most commonly misunderstood pollutants in air filtration engineering. Many facility managers treat smoke as though it was conventional dust – they buy a standard pleated filter and are surprised when they still have odors, haze and complaints.

The truth is that smoke is both a particulate pollution and gas-phase contamination issue. There is, therefore, a need for a number of separate filtration processes to be employed to deal with smoke effectively — which is why smoke odor filtration is engineered separately from particle capture.

This guide is intended to explain how smoke removal air filters work, why smoke air filters have to be HEPA filter for smoke, and through which processes activated carbon smoke filter work. It will also provide an overview of the selection, sizing and expected performance of smoke removal air filters.

In this guide you will also discover how DEIIANG manages its industrial smoke filtration – through a focus on media selection, contact time, pressure drop and monitoring performance rather than turning to filters only as a commodity item.


The Technical Challenge: The Concept of Smoke as a Mixture

Smoke is different from dirt. It is a dynamic system of aerosol that consists of solid matter, condensed water droplets, and a complex mix of gas. When you see smoke, you are actually seeing light being scattered by tiny particles — a fact that shapes tobacco smoke removal, wildfire response, and workshop fume control alike. The odor of smoke can be attributed to the presence of VOCs, acidic gases, and other aromatic substances which cannot be removed by a filter.

The distribution of particles in smoke depends on the type of fuel used, combustion temperature, condensation characteristics, and duration of time for which the smoke remains in the air. EACH of the different sources of smoke will have its own particle distribution. Therefore numerical figures should be considered for particular applications, and the figures should be verified with data from measurement or literature [1][6].

It is this mixed behavior that has made it necessary to have more than one stage since in this situation one stage is not effective for smoke removal and gas removal simultaneously. A particulate filter can remove the haze from the air, but it cannot completely remove the odor. A stage that contains only carbon is able to remove odor, but it cannot withstand soot particles and oils. It is necessary to specify effective smoke removal filters as systems.

Particulate matter and gas behave differently in the filter. Particulate matter is intercepted and diffused on the fiber surface, while gas is captured through adsorption. The following table explains the differences between contaminant types, and why an activated carbon smoke filter sits downstream of particulate media.

Contaminant types in smoke and their primary filtration technologies
Contaminant TypeTypical NatureExamples in SmokePrimary Filtration TechnologyStandard Media
Solid particulatesFine/ultrafine particlesSoot, ash, metal oxides/PM2.5Interception, impaction, diffusionHEPA/high-efficiency fiberglass
Liquid dropletsCondensed aerosolOil mist, tar aerosol, condensed organicsCoalescence followed by drainageCoalescing pre-filters
Gaseous VOCsMolecularBenzene, formaldehyde, acroleinPhysical adsorptionActivated carbon
Acid gasesMolecularSO2, HCl, NOxChemisorptionImpregnated carbon
Odor compoundsMolecular, traceAmmonia, mercaptans, aminesAdsorptionActivated carbon
Contaminant types in smoke (simplified)
ContaminantExamplesStandard Media
Solid particulatesSoot, ash, PM2.5HEPA/fiberglass
Liquid dropletsOil mist, tar aerosolCoalescing pre-filter
Gaseous VOCsBenzene, formaldehydeActivated carbon
Acid gasesSO2, HCl, NOxImpregnated carbon
Odor compoundsAmmonia, aminesActivated carbon

The figure below explains how each filter stage is designed to capture different components of smoke — and why buyers asking "are there air filters specifically for smoke removal" get a qualified yes.

Principle diagram comparing smoke composition — particulate phase, liquid droplet phase, and gas phase — mapped against HEPA and activated carbon capture zones

The diagram maps the three phases of smoke against the two main capture mechanisms. The particulate band is handled by mechanical filtration; the gas band requires adsorption media, so a HEPA filter for smoke alone cannot do the whole job.

Figure 1: Smoke composition mapped against filter capture mechanisms.


Which smoke type do you want to control?

Before selecting smoke control air filters, determine the source of the smoke. Wildfire smoke, tobacco smoke, welding fumes, soldering fumes, kitchen smoke, laser fume, and emissions from cleanroom processes have varying loadings of particles, gas composition, and requirements for safety and ventilation. A system that works effectively in one application may not work in another.

The table below serves as an initial guideline. It is only a useful screening method, not a final design template for industrial smoke filtration. Each application must comply with applicable local codes and establish compliance with occupational exposure limits.

Smoke sources and recommended filtration stages
Smoke SourcesPrimary Airborne ParticlesPrimary Airborne GasesRecommended Filtration StagesAirborne Source Capture Required?Limitations
Smoke from Wildfires and Forest FiresFine and ultrafine combustion particlesVolatile organic compounds (VOCs), aldehydes, acrolein, and carbon monoxidePre-filters and HEPA filtersNoAlthough HEPA filters do not eliminate carbon monoxide, filter bypass and fit are important considerations.
Smoke from Cigars, Cigarettes and PipesFine and ultrafine solid particles and tar aerosolVolatile organic compounds (VOCs), nicotine, and aldehydesPre-filters and HEPA filtersYesFiltration will not entirely eliminate the risk of exposure to the smoke produced by cigars and cigarettes indoors.
Smoke from Welding ProcessesPollution and fine particulate welding fumesChlorinated VOCs (VOCs), nitrogen oxides (NOx) and metal vaporsSpark arrestors, pre-filters and HEPA filtersYesAircraft must be evaluated on-site to determine airflow patterns.
Smoke from Soldering ProcessesDry contamination and fine particulate welding fumeFormaldehydes and VOCsPre-filters and HEPA filtersYesFilters become clogged with oily contamination and therefore fail to filter effectively.
Smoke from Cooking ProcessesGrease or combustible hydrocarbonsOdors and VOCsPre-filters and HEPA filtersYesHEPA filters are not to be used as substitutes for the listed components.
Smoke Produced from Laser and Surgical DiagnosticsFine and ultrafine particlesVolatile organic compounds (VOCs)Pre-filters and HEPA filtersYesProper local exhaust systems are required for treatment in individual cases.
Smoke from Specialized Overall ProcessesContaminants specific to particular processesAcid gases and basesCartridge filters and either HEPA or ULPA filtersYesClassification of the particles does not ensure the removal of the gas.
Smoke sources (simplified)
Smoke SourceKey GasesStagesSource Capture
WildfiresVOCs, COPre-filter, HEPANo
TobaccoVOCs, nicotinePre-filter, HEPAYes
WeldingOzone, NOxSpark arrestor, pre-filter, HEPAYes
SolderingAldehydes, VOCsPre-filter, HEPAYes
CookingOdors, VOCsPre-filter, HEPAYes
Laser and surgicalVOCsPre-filter, HEPAYes
Specialized processesAcid gases, basesCartridge, HEPA/ULPAYes
Key Point: Recirculating filtration systems may be appropriate for some uses; however, they should not replace the need for exhaust. In cases involving carcinogenic, toxic, infectious, or otherwise harmful contaminants, exhaust is preferable to recirculation. Investigate the details of the contamination, current local laws, and limitations on exposure to hazardous materials at work in addition to the regulations or limitations that govern the disposal of such items before proceeding with the release of air back to a work space populated by people.
Four common smoke sources compared side by side: wildfire haze over a distant city, tobacco smoke rising indoors, welding fume at a workstation, and kitchen smoke above a frying pan

Wildfire haze arrives as a dilute regional aerosol, while tobacco, welding, and kitchen smoke are concentrated local sources that are best handled at the source.

Figure 2: Four smoke sources with very different behavior.


Filter-Selection Matrix

The matrix below provides guidance for determining the composition to use in a smoke-capture system. This matrix should be used only as a design tool.

Filter-selection matrix by application
ApplicationPre-filterParticulate StageGas MediaRecirculationMonitoring
Forest FiresYesHEPAActivated CarbonYesIndoor PM2.5, CO
TobaccoYesHEPATreated CarbonLimitedPM2.5, VOC screening
SolderingCoalescingHEPAActivated CarbonYesPressure drop, VOC screen
WeldingSpark arrestorHEPATreated CarbonLimitedPressure drop, fume screening
KitchenGrease filterHEPA (protected)CarbonLimitedPressure drop
Laser and SurgeryYesHEPAActivated CarbonLimitedPressure drop
Combustion ExhaustYesHEPAActivated CarbonLimitedGas-specific monitoring
Filter-selection matrix (simplified)
ApplicationStagesRecirculation
Forest FiresPre-filter, HEPA, carbonYes
TobaccoPre-filter, HEPA, carbonLimited
SolderingCoalescing, HEPA, carbonYes
WeldingSpark arrestor, HEPA, carbonLimited
KitchenGrease, HEPA, carbonLimited
Laser/SurgeryPre-filter, HEPA, carbonLimited
Combustion ExhaustPre-filter, HEPA, carbonLimited

Following the Deiiang Multistage Approach

Since there isn't a single filter that does everything, all of the Deiiang engineers have designed smoke-abatement systems based upon the three-staged approach; that is, each stage makes use of and ensures that the prior stage protects the next one while maximizing the lifespan of the filter media. Incorporating a pre-filter, which is a fraction of the cost of a HEPA filter, can considerably extend the service life of the downstream system.

The underlying principle is simple: eliminate the larger and oily particles first, accumulate the smaller particles in the middle stage, and leave behind the vapor phase to be polished at the final stage — the staged logic behind every smoke removal air filter train. If any stage is not implemented, the downstream filter either blocks up, or breaks down early.

In the typical industrial cigarette smoke filter arrangement, there are three main stages:

  • Pre-filter: This stage eliminates large particles of soot, dust, and oil, which helps prolong the life of the filters that follow.
  • HEPA: This stage removes small smoke particles, including the sub-micron particles that create haze.
  • Activated Carbon: Finally, gaseous and odor adsorbents are used to absorb any remaining undesirables.

In heavy oily smoke situations, Deiiang sometimes specifies the use of fiberglass filters with F5-F9 implementation as the initial filter. These filters perform to temperatures of 150°C, have a high capacity for dust load and come in common sizes of 592×592×381 mm.

In the case of new specifications, ISO16890 ePM1, ePM2.5, and ePM10 ratings must be used instead of EN779 grades. These values are often related with U.S. HEPA standards, and buyers should treat the MPPS figure as the true rating of a HEPA filter for smoke duty. On the contrary, the classification of H13 and H14 is commonly classified based on EN 1822 or ISO 29463 which is based on the MPPS performance [4]. The customers must verify standards applicable to the stated value.

Frames are either made from aluminum, galvanized steel, and stainless steel with PU two-component sealant and EVA hot-melt separators. Airflow is rated between 1000 to 2500 m³/h with a maximum temperature of 70 °C and maximum relative humidity of 80%. Each filter is subjected to a separate factory aerosol test.

An explanation of aerosol testing: The term "DOP" is often used in a colloquial manner. Tests done in practice use either PAO or any other suitable aerosol. A complete test record must state the aerosol, the testing method, the applicable standards, and the acceptance criteria. Deiiang provides test records and can assist in tests done on-site.

In the gas phase, activated carbon smoke filters contain a deep carbon filter bed. Shallow carbon smoke panels are common errors in smoke filtration because the residence time is too short for proper adsorption.

Cutaway view of a multistage smoke abatement unit showing the bag pre-filter, H13 HEPA box filter, and activated carbon filter in series with airflow direction arrows

The staged train: bag pre-filter first, H13 HEPA second, activated carbon last. Each stage protects the next — the architecture used in every Deiiang smoke removal air filter.

Figure 3: Cutaway of a staged smoke abatement train.

Deiiang Product Data (verified)

The following table summarizes the critical product data information for verification. Values shown in this table are indicative unless stated otherwise. The buyers should ask for the relevant datasheet and test report.

Verified Deiiang product data
ProductModel / GradeNominal AirflowEfficiency BasisTemperature LimitHumidity LimitTest Documentation
Medium-effect fiberglass bag filterF5–F9 (EN 779 legacy)2050 m³/h at 592×592×381 mm45–95% at 0.5 µm150°CConsult datasheetFactory batch test
DOP integrated HEPA filterH131000–2500 m³/h99.97–99.99% at 0.3 µm70°C80% RHIndividual factory scan
DOP integrated HEPA filterH141000–2500 m³/h99.995–99.999% at 0.3 µm70°C80% RHIndividual factory scan
Super high efficiency baffle-free filterULPA U15–U17Consult model0.12 µm ratedConsult modelConsult modelIndividual factory scan
FFU moduleStandardFace velocity 0.45 m/s ±20%HEPA or ULPA dependentConsult modelConsult modelFactory test
Deiiang product data (simplified)
ProductGradeEfficiencyTemp Limit
Fiberglass bag filterF5–F945–95% @0.5 µm150°C
HEPA filterH1399.97–99.99% @0.3 µm70°C
HEPA filterH1499.995–99.999% @0.3 µm70°C
ULPA filterU15–U170.12 µm ratedConsult model
FFU moduleStandard0.45 m/s ±20%Consult model

The chart below is a conceptual illustration of staged performance. It is not a product performance certificate.

Figure 3: Cutaway of a staged smoke abatement train — bag pre-filter, H13 HEPA, activated carbon. Certified stage performance should be confirmed with model-specific test reports.

Activated Carbon Selection: What Buyers Need to Specify

"Deep carbon bed" and contact time alone are not enough to specify a gas-phase filter. Buyers should request carbon mass, apparent density, adsorption capacity, bed area, and breakthrough data for the target gases. These are the specifications that separate a serious activated carbon smoke filter from a marketing label. The following checklist covers the minimum information required.

Carbon type and impregnant: Coconut shell for general VOCs, coal-based for broad-spectrum adsorption, impregnated carbon for acid gases or ammonia.
Carbon mass by module: Total carbon mass of the media should be considered, not only bed volume.
Bed thickness and surface area: Important in terms of contact duration and drop of pressure.
Rated airflow rate and initial resistance: Rate must be according to fan rating.
Apparent density: It's a basic quality criteria but does not reflect adsorption ability. ASTM D2854 tests only apparent density; therefore, it proves no claims regarding smoke removal.
Systems for ratings are the following: Butane rating, iodine rating, breakthrough data.
Maximum recommended temperature and humidity limits reduction: Amount of moisture must be controlled as it affects the amount of available adsorption.
Carbons are not used against carbon monoxide and for other gases.
The methods of removing VOCs or odor would not be effective if there are no tests results about specific chemicals.

Engineering Features for System Design

Smoke filtering is a compromise between air changes and contact time — the two variables that decide whether a commercial air filtration system delivers. An air change rate defines what speed of purification is required, while the contact time affects the efficiency of carbon filtration. If one is too high, the other will be low.

Although air change rate can help in choosing an appropriate self-contained system, it can't show if source control is sufficient for immersion in mist. Instead, a system should use source-capture extraction instead of simple dilution — the first rule of industrial smoke filtration.

In order to provide 12 air changes per hour (ACH), it is necessary to have 1,200 × 12 = 14,400 m³/h of air flow within the ventilation system. This is a large system indeed.

The contact time for performance is calculated through the ratio between the carbon bed depth and the face velocity — a core concept in air filtration engineering. For a 50mm depth at a face velocity of 1.0m/s the contact time is measured to be 0.05 seconds, which is often deemed too short to allow for meaningful adsorption. The contact time for a 200mm depth at similar velocity is measured to be 0.2 seconds.

The engineering team at Deiiang typically starts with the performance specification range of 0.1 – 0.4 seconds; however, the specific time will depend upon the contaminant type, concentration, humidity and target outlet contaminant level.

The key steps in design include:

  • Determining the design airflow as a function of room volume, contaminant generation rate and desired cleanliness or exposure level.
  • Confirming source capture requirements and hood capture velocities before relying on room dilution for performance.
  • Controlling static pressure drop through multiple filter stages by using the specific model performance data.
  • Selecting the appropriate carbon type based on the actual target contaminant gases and the breakthrough criteria.

As a general rule, Deiiang uses Q = ACH × V / 3600 to size systems in metric m³/s. For example, the hood capture velocity for a welding bay with a contaminant generation rate of 0.5kg/hr would normally be estimated to be in the range of 0.5 – 1.0m/s. However, specific velocities vary based upon hood configuration and placement distance, air movement forces, temperature and energy produced by the work process. This must no doubt be confirmed by using recognized ventilation criteria and by performing smoke testing in a real working environment.

Budgeting for Pressure Drop

Budgeting for pressure drop can be somewhat complex in a three-stage set up. The chart that follows is a template for determining pressure budgets. Actual values should be taken from the certified product data.

Pressure budgeting template
StageFilter ModelMax AirflowClean ResistanceRecommended Change-Out ResistanceEstimated Loaded ResistanceFan Reserve
Pre-filterF7 bag2,050 cfmTBD as from data sheetTBDTBDTBD
HEPAH131,000–2,500 cfmTBD as from data sheetTBDTBDTBD
CarbonDeep bedApplication SpecificTBD as from data sheetTBDTBDTBD
Pressure budgeting template (simplified)
StageModelData Required
Pre-filterF7 bagClean and loaded resistance
HEPAH13Clean and loaded resistance
CarbonDeep bedClean and loaded resistance

A common mistake in establishing a proper efficiency for a final stage is not taking into account the pressure load that it places on the fan — a classic air filtration engineering mistake. If the fan curve cannot provide the design airflow at the loaded pressure, there will be under-performance of the system, even if it is believed that the filter is doing as it should.

Fire, Explosion and Process Safety Screening

Industrial smoke filtration systems may be subject to the risk of sparks, hot particles, combustible materials, flammable vapors or chemical reaction. HEPA and carbon media may present opportunities for fire load if misapplied. Safety screening should be done before media selection.

Spark arrestors and pre-separators where hot particles exist.
Temperature monitoring and temperature alarms.
Combustible dust assessment wherever dry particulate accumulates.
Grounding and bonding of duct work and filter cases.
Fire resistance construction and clearance as appropriate.
Safe carbon disposal procedures.
Local fire and explosion protection codes.

Filter Efficiency vs Clean Room Effectiveness

Laboratory filter efficiency does not necessarily equal room contaminant control. Bypass leakage, poor mixing, continuous generation of source contamination, leakage from the ducts, short circuit airflow through the duct, and infiltration of outside air all compute on the actual performance as you may expect it.

Effective clean airflow is device airflow times single pass removal efficiency, multiplied by bypass and installation losses. The fact that a purifier has an airflow of 1000 m³ per hour and a collection efficiency of 99% in a single pass does not mean that a flow of 1000 m³ is obtained. The emission of 990 m³ of clean air equivalent is achieved, and for calculating the size of recycling devices, differences of this kind are important.

Testing after Commissioning

The commissioning process ensures that an installed system is working according to the original design, which is where most air filtration engineering assumptions get tested. Various verifications should be carried out and recorded.

Balancing of airflow through all branches.
Making a reading of the pressure at all stages.
Checking whether the filters have been properly installed, ensuring that gaskets and seals are in perfect condition.
Carrying out an integrity test on the HEPA filter if necessary.
Undertaking particulate testing at different locations.
Sampling of gases for different pollutants.
Carrying out verification of the fume hood capture using smoke visualizations or velocity measuring methods.
Measuring noise in relation to the established project criteria.
Confirming controls and alarms.
Establishing baseline data for reference in the future.

Example Project: Deiiang Industrial Fume Extraction Project

The details of Deiiang Industrial Fume Extraction Project are presented below. Numerical values provided throughout this summary will be anonymized in some cases.

A precision electronics assembly has a 300 m² soldering and rework area in which the process emits rosin soldering fumes containing visible haze, odor, and VOC levels. The current single-stage filter system needs cleaning after every three weeks and does not control odor emissions, increasing the chances for the facility to fail its own air quality audit.

Details of the project:

  • Nature of the project: Solder fume extraction and VOC abatement retrofit in the precision electronics assembly section with an area of 300 m².
  • Year and location of the project: Asia-Pacific, 2025, client details withheld.
  • Project Challenges: The oily rosin aerosol resulted in prompt filter plugging, ongoing odor complaints, limited available capacity of the fans, and the need for production to be maintained throughout the installation.
  • Deiiang Approach: An advanced multi-stage air handling apparatus employing F7 glass fiber bag pre-filters (592 mm × 592 mm × 381 mm, each capable of handling up to 2050 m3/h of air), H13 DOP-integrated HEPA filters fitted with aluminum frames, and a coconut-shell deep-bed activated carbon filter with a contact period of approximately 0.2 seconds.

The retrofitting project reused an existing fan by minimizing the pressure drop in the pre-filters with a presumption of reduced filter bed pressure — a reminder that any HEPA filter for smoke lives or dies by pressure budget. Installation of the apparatus took place over the course of a weekend.

Verification of the multi-stage apparatus included determining the airflow, measuring the pressure, and conducting an on-site HEPA integrity test using an approved aerosol, plus carbon-stage checks that are standard in serious smoke removal air filter installations.

On-site photo of an installed multistage smoke extraction system at a welding workshop, showing the filter unit, flexible extraction arms, and labeled main and branch ducts

The installed system: labeled main duct, branch lines, flexible extraction arms, and the central filter unit.

Figure 4: Installed multistage smoke extraction system.

Comparison of Results pre and post Retrofit:

Before and after results with methodology notes
ParameterPre retrofitPost retrofitDifferenceCommentary
Particle count (≥0.5 µm, particles/m³)3.8 × 10⁷2.1 × 10⁵~99.4% decreaseCarried out using handheld particle counter and various locations after retrofitting
Detection and Quantification of VOCs (ppm isobutylene equivalent)4.20.3~93% decreaseBased the detection and quantification of VOCs on PID with 10.6 eV lamp
Perceived intensity of odor (1-5 scale)41DecreasedUsing informal panel; generation of data was not done in controlled manner
Change of filter frequency~3 weeks~14 weeks~4.7 times longerBased on the trend of pressure-drop
Cleanliness statusPreviously no classificationNow classified as project meeting specificationsProject meets objectivesBased on project acceptance test, not full iso 14644-1 classification
Before and after results (simplified)
ParameterPre retrofitPost retrofitDifference
Particle count ≥0.5 µm3.8 × 10⁷ /m³2.1 × 10⁵ /m³~99.4%
VOC screening4.2 ppm0.3 ppm~93%
Odor intensity (1-5)41Decreased
Filter change interval~3 weeks~14 weeks~4.7×
Cleanliness statusNot classifiedMeets project specsMeets objectives
Notes on Methodology: particle counts were gathered using handheld counter within predefined locations. VOC readings gathered using PID having 10.6 eV lamp are being shown as isobutylene equivalents. The readings gathered are in nature of screening response and should not be considered or interpreted as total VOC concentration since response factors vary for each kind of chemical compound. The scale of odor measurement was informal and should not be considered as a certified measure. Cleanliness results provide documented test conditions for acceptance criteria of the project and should not be interpreted for a full ISO 14644-1 classification.

The facility reported a reduction in the number of odor complaints as well as decrease in quantity of deployed filters in first year of adoption. Before conducting any cost-benefit analysis, the analysis of annual amount of filter, costs per unit filter, labor hours along with disposal cost and energy consumption have to be performed in conjunction with the adoption cost so that both of them could be analyzed.

This case study has been documented as project summary. Individuals considering similar industrial smoke filtration systems should request the anonymized reports of testing, photographs of deployment along with field deployment documentation.

When it Comes to Cleanroom Filtration

Certain facilities require both smoke suppression and cleanroom particle classification. Although connected, these are two different categories: cleanroom air filters are selected for particle concentration limits, not gas or odor load. cleanroom classification is according to iso 14644-1 and looks at airborne particles [2]. Therefore, it does not indicate that there is gas or odor elimination.

For applications with strict purity levels needed, such as wafer manufacturing or atomic research, Deiiang offers Super High Efficiency Baffle-Free Filters (ULPA U15-U17) with a rating of 0.12 µm using US HV ultrafine glass fiber paper. In cleanroom applications, FFU modules operating at 0.45 m/s ±20% are used for terminal filtration applications.

These products do not typically apply to smoke removal, but they can serve an important purpose if a smoke-free environment must also achieve stringent cleanliness classifications, where cleanroom air filters and smoke-duty carbon stages are specified side by side. Molecular contamination control design remains an independent requirement.


Design Factors Determined by Region and Locale

Deiiang uses local data to inform its designs because climatic, regulatory, energy cost, outside air quality, and ventilation practices shape conditions differently in each location. The following chart depicts how design will change, depending upon region.

Design considerations by region
Region TypeHigh Design FactorImplication for FiltrationMonitoring Priority
Humid TropicsMoisture HighHumidity determines untreated carbon limitations; hydrophobic or impregnated is preferredHumidity, pressure drop
Dry Industrial RegionDust HighPrefilter capacity and replacement frequency greatly impacts filtrationPressure drop, dust loading
Cold ClimateOutdoor Air Quality Low in WinterRecirculation with filtration may be preferredIndoor PM2.5, CO
Wildfire RegionOutdoor Air Quality high PM2.5 through SeasonBuilding level HEPA and carbon; fit of filter is significantIndoor PM2.5, CO
Design considerations by region (simplified)
Region TypeKey FactorMonitoring
Humid TropicsHigh moistureHumidity, pressure drop
Dry IndustrialHigh dustPressure drop, dust loading
Cold ClimateLow winter outdoor air qualityIndoor PM2.5, CO
Wildfire RegionSeasonal high PM2.5Indoor PM2.5, CO

Regional data should come from a respected entity in the region and include year of data used. Deiiang does not publish the pollution or climate data of cities without citing the source.


Wildfire Smoke Problems

Smoke coming from wildfires is a prevalent reason why many buyers look for air filters that can eliminate smoke, and a properly specified wildfire smoke air filter is central to any building response. When it comes to the actions that can be taken to deal with this issue, there are a number of possible building response approaches.

This includes:

Assess the building envelope leakages and close down any unneeded openings.
Limit the intake of outdoor air when the outside concentration of PM2.5 is high, while ensuring compliance with minimum ventilation regulations.
Use central HEPA filtration when possible, especially when it comes to air-conditioning systems that are able to cope with the pressure drop.
Set up portable HEPA equipment for the establishment of a clean-air environment inside.
Employ activated carbon or any treated media for the purpose of removing odors and gases.
Monitor PM2.5 and CO levels inside the building.
Make sure the filters are inspected afterward and changed if necessary.
Meaningful limitation: HEPA filters do not eliminate carbon monoxide as well as that standard activated carbon cannot be used for eliminating CO. This means that monitoring and source control become separate issues.

Smoke from Tobacco

Tobacco smoke removal is harder than most buyers expect: the smoke contains solid particles, tar aerosol, and gas mixtures. The use of filtration equipment restricted airborne particles and decreased the odor in rooms, but it cannot make smoking indoors safe. Preferably, smoking should be eliminated completely so that you do not expose anyone to smoking.

However, where filters are in use, the use of HEPA filter for smoke combined with an activated carbon smoke filter can also eliminate cigarette smoke and prevent the spread of smoke. This approach supports tobacco smoke removal and improves smoke odor filtration in enclosed spaces.

Commercial Applications

Commercial smoke problems differ from industrial ones. Kitchens, smoking lounges, hotels, warehouses, and offices each have distinct requirements for a commercial air filtration system — no single smoke removal air filter covers all of them.

Commercial smoke applications
ApplicationPrimary IssuesSuggested SolutionsMain Warning
Commercial kitchenSmoke, humidity, smellCode-approved grease removal and ventilation; carbon for odor eliminationHEPA is not an alternative to necessary kitchen exhaust components
Smoking loungeParticles, gas, etc.Source separation; supplementary HEPA and carbonNo means completely avoid risk
AccommodationOdor and cigarette residueSource control; HEPA and carbon in all affected areasSurface residue will need cleaned, not just filtered
WarehouseDiesel or process smokeSource capture; ventilation; filtration as neededCO and NOx demand specific controls
OfficeWildfire smoke and urban PMHEPA and carbon at building levelFilter fit and bypass considerations
Commercial smoke applications (simplified)
ApplicationSolutionMain Warning
Commercial kitchenGrease removal, ventilation, carbonHEPA not a substitute for exhaust components
Smoking loungeSeparation, HEPA, carbonRisk cannot be fully avoided
AccommodationSource control, HEPA, carbonSurface residue needs cleaning
WarehouseSource capture, ventilationCO and NOx need specific controls
OfficeBuilding-level HEPA and carbonFilter fit and bypass matter

What Smoke Filters Cannot Do

Prior to outlining any system, please be sure that expectations are in line with filtration's capabilities — and with what smoke odor filtration can and cannot adsorb.

  • They do not remove carbon monoxide using standard HEPA or activated carbon.
  • They do not replace oxygen.
  • They do not ensure regulatory exposure compliance on their own.
  • They do not get rid of third-hand smoke residues.
  • They do not substitute for source control or required exhaust ventilation.
  • They will not fix poor capture, duct leakage, or airflow short-circuiting.

Lifecycle Management and Performance Evaluation

Filters are consumables. They operate according to variable efficiency, and a filter working well at installation may fail within 6 months without drawing attention to itself. A smoke removal air filter system deteriorates in two ways: particulate steps load and create a greater pressure drop and carbon stages reach saturation and lose adsorption capacity with no visible indications.

Alarm setpoints must be determined according to manufacturer-recommendations with respect to final resistance, supply air available from fan, energy cost, process risk, and relevant operating experience and not general percentages applied universally. The practice of 60% or 80% is internally established and must be verified with regards to each process.

Best practices include:

  • Install differential pressure gauges at every bank of filters and setpoints per manufacturer specific standards.
  • Schedule regular air quality monitoring, because carbon breakthrough is not detectable visually.
  • Prevent carbon media oversaturation to avoid breakthrough.
  • Record baseline pressure readings during installation with weekly trending.

Sudden changes in pressure across HEPA filter may indicate seal or media failure; ascending pressure across a carbon filter signifies proper operation. It is preferable to monitor gases directly with gas analysis instead of relying on odor detection.

Monitoring Options for Carbon Breakthrough

PID meters have analyte-specific limitations. Utilizing odor detection as a primary alarm source is inappropriate and could potentially lead to a dangerous situation. Options for monitoring are outlined in the table below; for smoke odor filtration stages, direct gas measurement beats odor complaints every time.

Carbon breakthrough monitoring options
ContaminantMonitoring ApproachDetection RangeMain InterferenceAppropriate Alarm MethodSampling Period
VOCs (general)PIDppm scaleResponse ratios may be differentTrend and thresholdWeekly to monthly
FormaldehydeDetector tube or dedicated sensorppb to ppmOther kinds of aldehydesThreshold warningMonthly
Acidic gasesDetector tube or dedicated sensorppm scaleHumidityThreshold warningMonthly
Carbon monoxideElectrochemical detectorppm rangeOther gasesContinuous alarmAlways
SmellEvaluation through a panelQualitativeAdaptationComplaint recordAs needed
Monitoring options (simplified)
ContaminantMethodSampling Period
VOCs (general)PIDWeekly to monthly
FormaldehydeDetector tube or sensorMonthly
Acidic gasesDetector tube or sensorMonthly
Carbon monoxideElectrochemical detectorContinuous
SmellPanel evaluationAs needed

You need to purchase monitoring equipment specific to the substances you are being tested for and calibrate them accordingly, especially for activated carbon smoke filter service life tracking.

Maintenance Safety and Waste Disposal

When loaded with particulate matter, the carbon filter could potentially contain hazardous metals or toxic pollutants. Thus, when handling, maintenance personnel need to be careful not to expose themselves.

Make sure the mechanism is isolated from the system before you take out the filters.
Wear proper personal protective equipment.
Utilize procedures for filtering out hazardous materials.
Handle spills and classify waste correctly.
Evaluate the waste before disposal as required by local ordinances.
Keep records for material disposal.

Cost of Ownership

Purchasing facilities need to take into account the airflow and operating hours, clean and loaded pressure drop, fan efficiency and electricity price, and the costs associated with filters, labor, and replacement frequency. Costs resulting from disposal and downtime must also be considered.

Annual energy consumption, annual consumables together with total ownership cost estimates for five years should be provided for all outputs and their assumptions provided — standard practice in industrial smoke filtration procurement. Estimated savings, however, is not to be regarded as guaranteed savings.

Lifecycle Replacement Planning

The various replacements cannot be based only on calendar time schedules alone. In places where high smoke loads are being dealt with 24/7, it may be necessary to change pre-filters every month and carbon filters quarterly. In places with low workload, time duration may be extended.

The variables are concentration of contaminants, volume of air, humidity and nature of smoke chemically. Special focus should be laid on humidity since it reduces the adsorption capacity of the activated carbon — a key derating factor when specifying any activated carbon smoke filter. Where humidity is high, hydrophobic or impregnated carbon grades are utilized.


Conclusion

Smoke removal cannot be treated as a filter purchase. It can be treated as an engineering problem whose answer is sought for. The answer to the issue "Do we have smoke removal filters?" is yes when systems are coordinated. A HEPA filter for smoke deals with particulate phase while an activated carbon smoke filter deals with gas and odour. Pollutants are pre-filtered using an appropriate pre-filter and then purified. When the system is designed appropriately, then there is no guessing involved.

If your facility is experiencing visual smoke, offending odors, or filter replacement too often, it probably has to do with the incompatibility of the smoke and the filtration stages. In most cases the fix is either a proper HEPA filter for smoke upgrade or an added activated carbon smoke filter stage. The engineers at Deiiang use localized information and measurements to size each stage of the system properly.

No matter if you need a commercial air filtration system for the kitchen of a restaurant, an industrial smoke filtration system for a welding workshop, or a wildfire smoke air filter strategy for a large facility, they apply that same air filtration engineering discipline.

When making contact with Deiiang for a consultation, please provide:

  • The source process and schedule.
  • Measured gas and particle concentrations, if possible.
  • The humidity and temperature.
  • Exhaust or recirculation need.
  • Available static pressure and current fan curve.
  • Electrical supply and installation space.
  • Applicable regulations and desired outlet concentration.

Now you have the first step to finding a real solution.


References

  1. ISO 16890-1:2016 — Air filters for general ventilation — Part 1: Technical specifications, requirements, and classification system based on the efficiency of the particulate matter (ePM). https://www.iso.org/standard/57835.html
  2. iso 14644-1:2015 — Clean rooms and other controlled environments — Part 1: Classification of air cleanliness by concentration of particles. https://www.iso.org/standard/53394.html
  3. EN 779:2012 — Particulate air filters for general ventilation — Determination of the performance of filtration. (Replaced by ISO 16890 in several areas.) https://www.en-standard.eu/bs-en-779-2012-particulate-air-filters-for-general-ventilation-determination-of-performace-of-filtration/
  4. ISO 29463 — High efficiency filters and filter media for particulate removal in air. https://www.iso.org/standard/69363.html
  5. ASHRAE Standard 52.2 — Method of testing general ventilation air cleaning devices for particle removal efficiency. https://www.ashrae.org/technical-resources/bookstore/standard-52-2
  6. EPA — Wildfire smoke and indoor air quality. https://www.epa.gov/indoor-air-quality-iaq/wildfires-and-indoor-air-quality
  7. NIOSH — Control of smoke from laser/electrosurgical procedures. https://www.cdc.gov/niosh/docs/hazardcontrol/hc11.html
  8. ASTM D2854 — Standard test method for the apparent density of activated carbon. (Note: only the apparent density is discussed and does not include adsorption.) https://www.astm.org/d2854-09r19.html
  9. IEST-RP-CC001 — HEPA and ULPA filters. https://www.iest.org/Standards-RPs/Recommended-Practices/IEST-RP-CC001