wap_menu MENU
X

How do I install a medium filter?

Jason Peng, an engineer at Deiiang Company

  • Author:Jason Peng

  • Cleanroom Engineering Technology Manager of Deiiang Company.

    Product R&D Manager of GDC Inc. Cleanroom Equipment Manufacturing Company.

    Executive Director of Guangdong Cleanroom Industry Association of China.

  • 2025-01-06  |  Visits:
There are seven steps involved in the installation of medium filters. First is to identify what kind of medium replacement filters are needed since filters vary depending on the duty and configuration. Second, it is necessary to stop and lock out the fan as part of the site's isolation procedure. Third, the older filter is to be removed along with any containment. Fourth, the housing should be evaluated and cleaned. Fifth, the orientation of the filter must be determined based on its air filter airflow direction. Sixth, the filter should be seated and sealed properly. At the final stage, the process is complete once the fan is turned back on and proper operation is verified.

Exact isolation, containment, and commissioning procedures should comply with the equipment manufacturer's instructions as well as the facility's procedures based on the design of the unit, housing, and other protocols. The above-mentioned steps can be used as a general framework for how to install a medium filter, and the site document must be used as the regulatory authority.

There is one point that needs clarification. There is an inconsistency with how the term medium is used with different suppliers and grading systems. Medium cannot refer to any one standardized filter class. It is therefore essential to verify the appropriateness of the filter based on other data such as the specified testing standard, classification, size, and other operating characteristics rather than simply by the term medium [1][2].

The data in this HVAC filter installation guide follows the steps involved in this undertaking: identification, verification, preparation, isolation, removal, installation, sealing, restarting, and verifying operations. Deiiang catalogue values can be used as supporting data wherever applicable and are placed within the relevant section as catalogue data. Every medium filter installation and HVAC medium filter replacement shares the same basic sequence.


IKySBZ9esWQ
video thumbnail

Identify the Medium Filter and Confirm System Requirements

Proper identification before you install an HVAC air filter will greatly reduce the possibility of any installation issues. A medium filter is defined as being between a coarse pre-filter and a high efficiency final stage filter, however, the exact functioning of this filter is dependent on the system design. Be sure to verify the position of the filter bank in the air flow path.

The arrangement shown here is an illustrative example only. Actual arrangements vary. Some systems place the medium stage after the coil, some use two medium banks, and some use no HEPA stage at all.

This HVAC filter installation guide therefore asks you to verify your actual air-handling unit (AHU) design and filter bank sequence from the design documents before presuming anything. Deiiang provides medium efficiency glass fibre bag filters, synthetic bag filters, plastic frame W-bank filters, activated carbon V-bank filters, and pleated filters while the most appropriate filter should be determined based on duty instead of label.

What qualifies as a medium-efficiency air filter?

Filter efficiency class comparison

There is not a single global definition of a medium efficiency air filter and classification is based on the test standard that the manufacturer uses. ISO 16890 provides for the classification of particulate matter in air filters via ePM1, ePM2.5, and ePM10. At this time the ISO 16890 serves as the current standard for the classification of filters used for general ventilation.

The previously used EN 779 standard in Europe is no longer being utilized since it has been withdrawn from use. However, there are many filters labelled F5 through to F9 that still exist in stock and in older specifications.

ASHRAE Standard 52.2 uses its own test method and reports a Minimum Efficiency Reporting Value, or MERV. MERV and the ISO 16890 ePM classes come from different test methods and reporting rules, so the two should not be translated into eACH other without a documented, qualified basis.

EN 1822 and ISO 29463 are the standards for high-efficiency and ultra-low penetration air filters. They do not classify medium filters, and a medium filter should never be described with an H13 or H14 grade.

Performance is also influenced by construction, and consequently the filter media, pleat or bag geometry, and specific applications. A medium filter could be installed upstream to HEPA if such is included in the design of the system. This does not mean that it can be included in every cleanroom and HEPA system.

Which system and filter specifications must be confirmed before installation?

Filter installation requirements checklist

Obtain the following data from approved drawings or from the existing installations and systems before following the rest of this HVAC filter installation guide. Do not depend solely on the nameplate of the equipment for these data.

  • Nominal face size and depth, in mm.
  • Rated airflow of the filter's test conditions, in m³/h.
  • Declared classification and related test standard.
  • Initial and final resistance, in pascals, at desired airflow.
  • Housing type such as side access rail, front access frame, flange joint.
  • Gasket type and retention method indicated by the housing manufacturer.

If required data is missing from the schedule, you must measure the housing before ordering, because you cannot install an HVAC air filter that does not match it. An incorrect depth of filter will not close, while an incorrect width filter will leak at the gasket, wasting filter utility and overloading subsequent stages of filtration. Every medium-efficiency air filter installation starts with this dimensional check.

Table 1: Filter categories, declared classification systems, intended stages of use, and compatibility checks.

Filter categoryDeclared test / classification systemTypical intended stageCompatibility checks prior to selecting
Coarse panelISO 16890, ePM10 or lowerFirst stage pre-filterFace size, depth, rails, airflow
Medium bag or panelISO 16890 ePM1 / ePM2.5 / ePM10; legacy EN 779 F5-F9 labels might continue appearing in the marketplaceIntermediate stage ahead of a final filter where the system design specifies itDeclared class, dimensions, rated airflow, initial resistance, gasket, housing instructions
High efficiency (EPA, HEPA, ULPA)EN 1822 / ISO 29463Final stageLeak tight housing, gasket or gel seal, validated test method
Filter categoryDeclared systemTypical intended stage
Coarse panelISO 16890, ePM10 or lowerFirst stage pre-filter
Medium bag or panelISO 16890 ePM1 / ePM2.5 / ePM10; legacy EN 779 F5-F9 labels might continue appearingIntermediate stage ahead of a final filter where the system design specifies it
High efficiency (EPA, HEPA, ULPA)EN 1822 / ISO 29463Final stage

Note: classification systems are not interchangeable. The table categorizes filters for orientation only. It does not declare any equivalency between systems.


Prepare the Work Area, Tools, and Replacement Filter

Preparation is what ultimately determines whether a medium filter installation can be achieved. A unit must be isolated, the work area protected, and the replacement inspected, prior to carrying it to the housing. During a cleanroom medium filter change, individual facility own contamination control rules take precedence over any amended order of a generic installation sequence.

All work should follow the approved maintenance and room recovery procedure established by the facility; this is the first rule of how to install a medium filter. If it is prior to opening anything, then occupy space assessing the relationships of pressure, production status, and neighbouring zones. Barriers or temporary measures should only occur after the facility responsible team approves an action.

The preparation checklist lists what has to be ready before work starts. The actual tool list and permit set will depend on the housing, filter type, and site permit to work requirements.

What tools and protective equipment should technicians prepare?

Technician tools and personal protective equipment laid out

Personal protective equipment (PPE) must be risk-based during any cleanroom medium filter change, and not based on constant factors. This entails taking into consideration the filter's history of usage, safety information, site risk assessment, and details of the applicable respiratory protection program to determine if P2 or N95 respirators are appropriate for the filter.

In situations whereby hazardous, biological, or unknown contaminants may be involved in a cleanroom medium filter change, the facility containment and disposal procedures apply. The procedures may include respiratory protective measures, skin protective measures, methods of decontamination, and procedures for proper disposal of waste which may extend beyond what is listed below.

Tools that may be generally used for a medium filter installation include:

  • Cut-resistant gloves and eyewear for frames and mesh.
  • HEPA-filter vacuum for cleaning the housing.
  • Lint-free wipes and approved cleaner.
  • Flashlight for inspecting gasket and bypass.
  • Calibrated differential manometer.
  • Retaining tools as specified by the housing manufacturer.

Improvised tools must not be added. If the housing requires an implement that is not available, stop working until the correct implement is obtained.

How should the work area and replacement filter be handled?

Technician handling a box of new replacement filters before installation

As this HVAC filter installation guide sets out, users should be notified before the unit shuts down. Next, shut down the unit using the regular controls, isolate the fan, and lock out other energy sources. Verify that the fan stops working and cannot be restarted immediately. Address remaining energy and moving dampers accordingly.

Do not automatically close the upstream and downstream dampers, as whether to isolate a bank depends on the design of the system in place and the pressure control procedure approved for that unit. Inspect the replacement filter when it arrives.

Inspect the frame for deformation, the media for rips, and the gasket for cracking or compression set; this pre-check decides whether a medium-efficiency air filter installation can proceed. Compare the label to the order: model, declared class, dimensions (width, height, depth), rated airflow, and initial resistance.

Keep the filter intact at the required location until the housing has been cleaned; this is a point that separates how to install a medium filter from a simple filter swap. A single page of pre-installation instructions will provide proper identification of the unit as well as other details like the approved filter type, isolation status of the unit, state of the housing, airflow arrow, gasket, and post-start information so that the process can be repeated.


Verify Filter Size, Model, and Performance

A filter whose dimensions are wrong by a few millimetres will bypass air, and one that is too large will not fit at all. Confirmation requires comparing several dimensions of the housing against the approved drawing and against what was actually delivered. This is the step where most HVAC medium filter replacement jobs either succeed or fail.

The measurement diagram shows where to take measurements. Any discrepancy is easily determined when the same points are used for both the housing and the filter.

How do you measure the filter housing accurately?

Technician measuring filter housing with tape measure

Use a tape rule and document everything in mm.

  • Face width: inside edge of flange to inside edge of flange.
  • Face height: upper rail to lower rail.
  • Depth: upstream stop to downstream stop.
  • Gasket groove dimension, if a groove is present.
  • Rail-to-rail distance at the insertion point and at the final seating position.

Compare this with the accepted drawing and the specification of the filter based upon published information. The requirements regarding acceptable clearance and gasket compression differ according to the frame type and specifics of the gasket and retaining design. The design must be adhered to the documented figures for that specific combination.

A general rule regarding clearance and compression does not apply when you install an HVAC air filter. In case of contradiction between the drawing provided and the filter received, the discrepancy should be settled prior to installation, and not forcing it into position. The situation must be rectified in case the housing is seen to be out of parallel; using a shim to correct this should be done upon approval from the manufacturer.

Which efficiency and operating data should buyers verify?

Filter efficiency operating data datasheet

One should verify the declared classification as well as the respective test standard, rather than simply verifying the grade, and do so before any medium-efficiency air filter installation. The dimensions, rated airflow at stated test condition, and both initial and final resistance at this airflow should be checked. The operating figures must correspond to previous values and the actual operating point of the system.

The rated airflow of the filter differs from the actual operating airflow of the air-handling unit. The pressure drop is dependent on both airflow as well as the configuration of the filter; as these factors are present, resistance figures for the operating point will deviate from the catalogue values.

The fan must be capable of supplying airflow to the system, against the resistance created by the total of the various components: the pre-filter, the medium stage filters, coils, ducts, dampers, and the final filter. The total resistance at the design airflow must sum all resistance figures thus far obtained, and ensure that an appropriate fan curve has been created which matches this total value.

A worked example requires actual fan curve and filter data to be located for the specific unit in question, which is why this article does not offer a single universal way to install an HVAC air filter. Substituting a lower-efficiency filter solely to overcome insufficient fan pressure is not advised, because that modifies the filtration function that the system was created to accomplish.

Table 2: Deiiang medium-filter catalogue data as summarised for this article.

Filter familyDeclared gradeFace sizeRated airflowInitial resistanceFinal resistanceMedia area
Medium glass fibre bag filter, 6-bagF5592x592x381 mm2050 m³/hbelow 50 Pa250-400 Pa3.18 m²
Medium glass fibre bag filter, 6-bagF8592x592x381 mm2050 m³/hbelow 100 Pa250-400 Pa3.18 m²
Medium glass fibre bag filterF6not stated in the cited catalogue2050 m³/hnot stated in the cited catalogue250-400 Panot stated in the cited catalogue
Medium synthetic bag filterF6, F7, F9not stated in the cited catalogue1000 m³/hnot stated in the cited catalogue250-400 Panot stated in the cited catalogue
Medium synthetic bag filterF5, F9not stated in the cited catalogue1700 m³/hnot stated in the cited catalogue250-400 Panot stated in the cited catalogue
Plastic frame W-bank combined filterF723x23x11.5 innot stated in the cited cataloguenot stated in the cited cataloguenot stated in the cited cataloguenot stated in the cited catalogue
Plastic frame W-bank combined filterF811.3x11.3x11.5 innot stated in the cited cataloguenot stated in the cited cataloguenot stated in the cited cataloguenot stated in the cited catalogue
Activated carbon V-bank combined filterfor removal of gases and odoursnot stated in the cited catalogue3700 m³/hnot stated in the cited cataloguenot stated in the cited cataloguenot stated in the cited catalogue
Filter family and gradeFace sizeRated airflow
Medium glass fibre bag filter, 6-bag, F5592x592x381 mm2050 m³/h
Medium glass fibre bag filter, 6-bag, F8592x592x381 mm2050 m³/h
Medium glass fibre bag filter, F6not stated in the cited catalogue2050 m³/h
Medium synthetic bag filter, F6, F7, F9not stated in the cited catalogue1000 m³/h
Medium synthetic bag filter, F5, F9not stated in the cited catalogue1700 m³/h
Plastic frame W-bank combined filter, F723x23x11.5 innot stated in the cited catalogue
Plastic frame W-bank combined filter, F811.3x11.3x11.5 innot stated in the cited catalogue
Activated carbon V-bank combined filter, for removal of gases and odoursnot stated in the cited catalogue3700 m³/h

Source note: the data in the table above have been taken from the Deiiang medium filter summary from the catalogue page used for this medium filter installation article. The summary does not state catalogue model numbers, so these numbers should be checked against the most recent revision of the Deiiang catalogue prior to ordering.

If more than one grade is included in a family, with the example grades being F5 and F9 in reference to the synthetic bag family, the grade on the shipping label must be confirmed before ordering.

The construction information from the catalogue includes the aluminium folding frame, along with the stainless steel option in certain models, glass-fibre bag media, polyurethane two-component sealant, a 120 g/m² adhesive board-paper divider, and sprayed diamond wire-mesh protective netting. The maximum temperature for the glass-fibre version is 150 °C and the maximum humidity is 100%. The synthetic version includes the aluminium profile frame but the operating temperature is restricted to 80 °C.


Shut Down the Unit and Remove the Existing Filter

The removal process is classified as containment due to the size of the medium filter's mass of dust, and this is the point in any HVAC medium filter replacement where contamination control matters most, therefore an optimal plan should be developed to ensure complete control of contamination at the source.

The diagram represents a general guideline; the specific requirements for an installation depend upon the type of removal procedure used and housing classifications.

How should the air-handling unit be isolated?

Air handling unit lockout tagout service isolation

Inform individuals affected by the situation and switch off the power to the air-handling unit, since a medium filter installation can only begin once the unit is dead. In accordance with site procedures, disconnect the energy sources. Confirm that the fan has stalled and will not restart by itself and then consider the existing stored energy such as capacitors and spring-actuated devices or movable dampers.

Unless the design and the pressure control strategy permit a different approach, isolate the filter section of the air handling unit. Do not isolate the dampers in the usual manner; for example, some equipment may still create an imbalance in room pressure or trap contaminants in incorrect areas. When isolating equipment, always follow the recommended procedures.

In the case of multi-bank systems, isolate the filter section one bank at a time whenever possible to keep dust emissions to a minimum, which is standard practice for how to install a medium filter safely. Remember to open the access panel slowly because the section ahead may be under a negative pressure.

How can the old filter be removed without spreading contaminants?

Worker bagging old dirty filter for disposal

Whenever possible, contain the filter before movement. You should not shake or compress the media. Simply follow the site waste and exposure control procedures for the specific contaminating material.

There are several validated techniques for filter containment, some of which may include bagging and/or wrapping the filter. Be aware that the binding or packaging method utilized may vary with each installation.

Once the filter has been taken from service, vacuum out the housing utilizing HEPA-filter vacuum cleaners and wipe down the adjacent areas, as any HVAC filter installation guide will insist. Inspect for corrosion, loose gasket material, and damaged clamps. Repair a defective housing before installing the new filter rather than compensating with extra sealant.


Install the Medium Filter in the Correct Airflow Direction

NivYhQL7Bg4
video thumbnail

The direction of the arrow on a medium filter is an essential indicator of the air filter airflow direction. The airflow passage of air is conveyed by the direction of the arrow on the filter. The filter may pass air even when incorrectly placed, but the efficiency of the filter and its operation will not function as planned. Getting the air filter airflow direction right is non-negotiable.

The arrow direction indicates the direction of airflow from the air inlet through the rest of the ductwork to the final filtered air location. Follow the airflow path to determine the air filter airflow direction before any installation.

How do you determine the correct airflow direction?

Filter airflow direction arrow installation

By tracing the path of air from the air return through the air intake through to the supply, which is how a medium-efficiency air filter installation confirms orientation. Upon confirmation of the direction of airflow the arrow marked on the filter must indicate downstream in the direction of the last section of ductwork. Reference the manufacturer's instructions and specifications to locate the marking properly.

In the event the arrow marking is missing or unclear, stop all work and obtain clarification in writing from the manufacturer before proceeding, because the air filter airflow direction cannot be guessed. Using either the opening of the bag that was used to store the filter or the position of the gasket on the filter will lead to incorrect placement.

If using a side access means of installation, verify that the arrow is pointed away from the access compartment and is located in view of the downstream ductwork, which keeps the air filter airflow direction correct. Record the orientation on the installation record for reference in the future.

How should the filter be seated and secured?

Seating medium filter into housing frame

Use the retention method specified by the filter and casing manufacturers when you install an HVAC air filter, whether it is clamps, pressure bars, a wedging system, or a bolted frame. Do not create a fastening pattern or tightening sequence on your own, nor use shims unless cleared by the manufacturer.

Slide the filter into position in the casing without forcing it through, which is the step most commonly got wrong in how to install a medium filter. If the frame catches on a rail, stop and assess the problem rather than forcing the filter through as this can cause damage to the frame, tear the media, or roll the gasket out of its place.

Once the filter frame is fully installed and the air filter airflow direction has been confirmed, secure it as instructed. Rather than putting sealant over a damaged or flattened gasket, replace the gasket. Rather than using shims, repair a defective casing. Make sure the filter cannot move once the access panel has been closed.


Seal the Housing and Check for Bypass

The bypass mechanism is the failure mode that most often allows an incorrectly selected medium filter to fail. Bypass air flows around the filter frame and is not filtered, which may cause accelerated loading of the downstream stage, depending on design considerations. For anyone learning how to install a medium filter, this sealing step is where the real work shows.

The diagram marks the perimeter gasket, the access panel gasket, and typical gap locations. It is a screening aid, not a leak-test procedure.

How can technicians identify gaps around the filter?

Filter bypass leakage gap

Utilize a smoke pencil, flashlight, or thermal anemometer as a means of screening for gaps. These instruments make it possible to identify the likely location of a leak easily; however, they cannot identify the existence of a leak. When accepting leakage levels, the weaknesses of these instruments must be considered in conjunction with the acceptance criteria established by the test method.

When placed in the vicinity of a leaking site, a smoke pencil moves toward the source of negative pressure or diffuses away from it in the presence of positive pressure. The light from the lamp along the gasket edge can help identify gaps in the gasket, with the downstream side of the gasket being illuminated in turn. Once a possible leak is identified, it is necessary to mark it before opening the panel again.

Which sealing checks prevent unfiltered air bypass?

Filter housing bypass closed and open flow direction cross section

Three paths must be checked:

Perimeter gasket: verify that it is intact and properly seated in the groove.
Access panel sealing gasket: confirm that it is intact, and the latch system uniformly compresses it.
Frame and housing interface: ensure that the frame is pushed into place and not able to slide.

In case a knife edge or gel seal is being used by the framing system, check to see that the filter's gasket resembles the knife edge and properly scrapes the track, and the gel seal is clean and wet. It will not seal if the gel seal is dry or contaminated, even if the filter sits in the right position.


Restart the System and Verify Operation

The system must not simply restart when the disconnecting means are closed, because a medium-efficiency air filter installation is not finished until airflow is re-established correctly; instead, the air handling device must be brought up to speed according to the specifications in order to stabilize the system for measurement of its air movement and differential pressure.

The criteria for passing an HVAC medium filter replacement come from the design schedule, the approved startup plan, and the manufacturer's documents, rather than a set universal criteria.

What should be checked before restarting the system?

Pre startup system checklist

Prior to powering the unit, tools, packing materials, and debris need to be verified to have been removed from the equipment area, because the way you install an HVAC air filter determines what is left behind. Ensure that the access panel is positioned correctly and locked. Ensure that all isolating devices are ready for operation in accordance with site procedures.

Verify the direction of motor rotation, if the motor has been reconnected. Ensure that the control equipment is in the correct operating mode. Implement the pressure control plan which will necessitate resetting the dampers that were moved during the isolation.

How can airflow and pressure drop be verified after installation?

Measuring filter pressure drop after installation

Allow the system to stabilize in accordance with the commissioning procedures, and take readings at designated test points using calibrated measuring devices; this closes the loop on how to install a medium filter. Take measurements of the airflow in m³/h and differential pressure in pascals across the filters at the actual operating mode.

Cross check these readings with the design values, commissioning baseline, and product information, since this is what closes out an HVAC medium filter replacement. Any variances might indicate clogged pre-filters, partially blocked dampers, filters that are improperly installed, or the presence of a bypass channel. The cause of the problem must be investigated rather than simply adjusted to achieve proper fan operation.

Only measuring the pressure drop cannot determine if the filter is located as it should be, or that bypassing is present, so an HVAC medium filter replacement must include a visual check. A low value can indicate a bypass just as easily as a clean filter. In cases where cleanroom classification, or filter integrity, needs to be demonstrated, it is an individual procedure carried out per the facility-approved protocol by trained personnel.

Table 3: Pre-start and post-start checks by stage, method, and evidence.

StageItem checkedMethod usedEvidence to be recorded
Before startEnergy isolation confirmedSite lockout procedureLockout tag and verification signature
Before startFilter in position and gasket goodVisual inspection checked against manufacturer drawingPhotograph, inspection note
Before startHousing and access panel cleanVisual inspection, HEPA vacuumInspection note
After startAirflow measured at documented pointCalibrated anemometer or flow gridReading in m³/h, instrument ID and calibration information
After startDifferential pressure across filter bankCalibrated manometerReading in Pa, operating airflow, fan setting
After startComparison to design and baselineDesign schedule and commissioning recordDeviation note and corrective action sign-off
StageItem checkedMethod used
Before startEnergy isolation confirmedSite lockout procedure
Before startFilter in position and gasket goodVisual inspection checked against manufacturer drawing
Before startHousing and access panel cleanVisual inspection, HEPA vacuum
After startAirflow measured at documented pointCalibrated anemometer or flow grid
After startDifferential pressure across filter bankCalibrated manometer
After startComparison to design and baselineDesign schedule and commissioning record

Document Maintenance, Troubleshoot Issues, and Apply Project Lessons

Medium filter maintenance should be data-driven. The filter communicates its status to the user via the differential pressure reading, and the record indicates if the change interval corresponds to the actual loading. Just keeping a log of dates does not suffice.

This image is a general illustration of a change-out in progress and not a photograph of the project described below. The monitoring interval and thresholds still come from the manufacturer's announced final resistance, the system design, fan capability, operating trend, and the maintenance policy.

What installation details and warning signs belong in maintenance records?

Maintenance record form installation details

Record the following for traceability:

  • Unique AHU and filter bank identification.
  • Filter model and batch or serial number information where available.
  • Declared standard and efficiency classification.
  • Installation position, including airflow direction.
  • Initial differential pressure at the documented airflow.
  • Instrument ID and calibration status.
  • Measurement locations and fan setting.
  • Inspection date and corrective action sign-off.

Warning signs are typically recorded when there is a noticeable pressure drop that is faster than historical data, an unexpected drop in pressure, visual dust formed on the downstream side of the system, or a damaged or flattened gasket at the final stage of the installation. It is essential to regard the planned replacement threshold as a planning tool while the final resistance stated by the manufacturer is the reference limit.

What can a real Deiiang installation case study demonstrate?

Cleanroom filter installation project site crew

The following cleanroom medium filter example is an illustrative composite based on a Deiiang project description. It is not a verified case record, and no measured outcome is claimed here.

An example of a medium filter installation is a pharmaceutical packaging cleanroom with limited plenum height and strict limits on pressure drop. The installation provided low-profile H14 high-efficiency filters rated at 592×592×292 mm, 2500 m³/h, 220 Pa or lower initial resistance, and 20.04 m² media area, along with F7 pre-filters and silicone-free gaskets.

In this installation, the specifics relate to the pre-installation step, including checking the F7 pre-filters for dimensions such as width and depth and confirming the direction indicated by the arrow marked on the filter. The pre-filter must be accurately seated in the shallow housing, since unsealed pre-filters will force dust onto the H14 filters.

Contributed note from Deiiang product designer Jason.peng: the most frequently reported issue is that a filter is pushed into a tight housing, which causes the gasket to roll out of its groove. Although it may appear that the frame is seated from the access side, a smoke test along the perimeter may show the gap.

If this happens, simply remove the filter, reset the gasket, and check that the rails of the housing are not deformed before reseating the filter.


Frequently Asked Questions

What is a medium filter?

A medium filter is one of many different levels of filtration and is considered finer than a coarse pre-filter but less efficient than a high-efficiency final filter. There are no universally defined criteria for what constitutes a medium filter, so check the formal designation and applicable test standards prior to calling it a medium filter. For ventilation purposes, use ISO 16890 as the standard currently in force.

How do I install a medium filter?

For medium filter maintenance, select the correct replacement filter; stop and lock out the fan per site procedures; remove the old filter and contain it; clean and inspect the housing; install the new filter in the proper direction according to the arrow indicating airflow; reinstall and seal the filter; then restart the fan and verify that proper airflow and differential pressure exist. Follow the equipment manufacturer's instructions and the site's approved procedures for isolation, containment, and commissioning.

How can I tell which way the filter should face?

A good habit in medium filter maintenance is to check the direction of air flow in the system first, and then determine that the arrow on the filter indicating direction points downstream towards the discharge. Go also by the manufacturer's label and drawing; if the arrow is unclear or missing, do not proceed until you have written confirmation.

Do I need to shut down the HVAC system before changing the filter?

Absolutely. Inform users, shut down the unit through its regular means, isolate and lock out energy sources according to the local policy, and check to see that the fan cannot come back on without action being taken. It is important to understand whether the dampers must be closed based on the design of the system and the plan for pressure control; follow the recommended isolation procedure established for the specific unit.

How do I know if the medium filter is installed correctly?

As part of medium filter maintenance, make sure that the frame of the filter is tight and secure, that the gasket has not been damaged and that its contact pressure complies with operating specifications, and that no gap exists in the screening tests. Be sure to record the flow of air and the differential pressure during checkout and compare to both the design conditions and standards previously established. Simple pressure drop does not indicate the proper installation.

How often should a medium filter be replaced?

Determine the replacement interval and criteria based on your facility's manufacturer's specified maximum acceptable resistance level for the filter, the design of your system, and the capabilities of the fan. Any referenced time period must be site-specific unless the manufacturer specifies otherwise in their documentation.


References

This list presents standards for orientation purposes and is not a definitive installation guide. Standards on test methods and classifications for high-efficiency filters include EN 1822, IEST-RP-CC001, ISO 29463, and MIL-STD-282. No generic installation instruction for a medium filter should be inferred from the inclusion of a standard.

  • [1] ISO 16890-1, Air filters for general ventilation — Part 1: Technical specifications, requirements and classification system according to the efficiency of particulate matter (ePM) filtration. International Organization for Standardization. https://www.iso.org
  • [2] EN 779, Particulate air filters for general ventilation — Determination of filtration performance. Withdrawn. The ISO 16890 series now applies to general ventilation. Status must be verified through an appropriate European standards organization. https://www.cencenelec.eu
  • [3] ASHRAE Standard 52.2, Method for Testing General Ventilation Air-Cleaning Devices for Efficiency at Various Particle Sizes. ASHRAE. https://www.ashrae.org
  • [4] EN 1822-1, High-Efficiency Air Filters (EPA, HEPA, and ULPA) — Part 1: Classification, performance testing, and marking. Current edition must be verified through an appropriate European standards organization. https://www.cencenelec.eu
  • [5] ISO 29463-1, High-Efficiency Filters and Filter Media for Particulate Air Filtration — Part 1: Classification, performance testing, and marking. International Organization for Standardization. https://www.iso.org
  • [6] iso 14644-1, cleanrooms and Controlled Environments — Part 1: Classification of Air Cleanliness by Particulate Concentration. International Organization for Standardization. https://www.iso.org
  • [7] iso 14644-3, Cleanrooms and Controlled Environments — Part 3: Testing Procedures. International Organization for Standardization. https://www.iso.org
  • [8] IEST-RP-CC001, HEPA and ULPA Filters. Institute of Environmental Sciences and Technology. https://www.iest.org
  • [9] MIL-STD-282, Filter Units, Protective Clothing, Gas Masks, and Related Products. Confirm current version through the U.S. defense department standards catalogue. https://quicksearch.dla.mil
  • [10] Deiiang medium-filter catalogue summary provided for this article. Cleanroom and air filter manufacturing company, cleanroomequips.com. Catalogue must be verified against the current Deiiang catalogue before ordering.

https://www.cleanroomequips.com/Air-Filter-FAQ/How-do-I-install-a-medium-filter-.html

Home

PHONE

Email

Inquiry