MENU
X

How to detect the temperature, humidity and noise of the clean room?

  • Author:Jason Peng

  • Cleanroom Engineering Technology Manager of Deiiang Company.

    Product R&D Manager of GDC Inc. Cleanroom Equipment Manufacturing Company.

    Executive Director of Guangdong Cleanroom Industry Association of China.

    Engaged in R&D of related products for 15 years, with rich relevant technical experience

  • 2024-11-18  |  Visits:

1. Before measuring the air humidity and relative humidity in the clean room, the purification Air conditioning system should have been running continuously for at least 24 hours. For places with constant temperature requirements, according to the requirements of the relative temperature and Relative humidity fluctuation range, the measurement should be carried out continuously for 8-48 hours, and the interval between each measurement should not exceed 30mm.

2. According to the temperature and relative humidity fluctuation range, the corresponding instrument with sufficient accuracy should be selected for measurement.

微信截图_20241118172513.png

3. The measurement points in the clean room are generally arranged at the following locations:

  • Supply and return air outlets;

  • Representative locations in the constant temperature working area (such as around the process equipment or at equal distances);

  • Center of the room (for systems without constant temperature requirements, temperature and humidity are only measured at this point):

  • At the sensitive element

All measurement points should be at the same height, 0.8m above the ground. They can also be arranged on several planes above the ground according to the size of the constant temperature zone. The distance between the measurement point and the outer wall surface should be greater than 0.5m.

4. The number of measurement points is determined according to the attached table.

Fluctuation   rangeRoom area ≤   50m2 Every additional 20-50m2
±0.5~±2℃
    ±5~±10%RH
           Increase 3-5
≤|05|℃
    ≤|5|%RH
The   point spacing should not be greater than 2m, and the number of points should   not be less than 5

Detection of noise in clean rooms

1. The noise measuring instrument is a sound level meter with an octave analyzer. Generally, only the A sound level is measured, and the octave sound pressure level is measured when necessary.

2. Measurement point location: It is advisable to set the points according to the attached figure. For those with an area of 15m2 or more, a point in the center of the room can be used; the height of the measurement point is 1.1m from the ground.

Latest Hot Articles

leave a message

Leave Your Message


LEAVE A MESSAGE

If you are interested in our products and want to know moredetails,please leave a message here,we will reply you as soon as we can.