Clean room inspection items
Serial number | project | One-way flow | Non-unidirectional flow | Enforcement | |
1~4level 5level | 6~9level | ||||
1 | Air volume supplied by the vent (total Air volume supplied by the system if necessary) | Unexpected | Must test | E1 | |
2 | Room or system fresh air volume | Must test | E1 | ||
3 | Room exhaust volume | Negative pressure clean room must be tested | E1 | ||
4 | Indoor cross-sectional Wind speed | Must test | Unexpected | E1 | |
5 | Wind speed unevenness | Must test | If necessary, measure | If necessary, measure | E3 |
6 | Air velocity at the air outlet or specific boundary | Unexpected | If necessary, measure | E1 | |
7 | Static pressure difference | Must test | E2 | ||
8 | Cleanliness at 0.6m inside the door after opening | Must test | Unexpected | E2 | |
9 | Wind speed at the opening | If necessary, measure | E2 | ||
10 | Formaldehyde concentration in the room | If necessary, measure | E13 | ||
11 | Ammonia concentration in the room | If necessary, measure | E14 | ||
12 | Ozone concentration in the room | If necessary, measure | E15 | ||
13 | Carbon dioxide concentration in the room | If necessary, measure | E16 | ||
14 | Supply air high efficiency filter scanning and leak detection | Must test | D2、E3 | ||
15 | Exhaust air high efficiency filter scanning and leak detection | Biological clean room must be tested | D2、E3 | ||
16 | Air cleanliness level | Must test | E4 | ||
17 | Surface cleanliness level | If necessary, measure | Unexpected | The standard is selected by negotiation between the client and the inspector. | |
18 | Temperature | Must test | E5 | ||
19 | Relative humidity | Must test | E5 | ||
20 | Temperature and humidity fluctuation range | If necessary, measure | E5.2 |
21 | Regional temperature difference and regional humidity difference | If necessary, measure | E5.2 | |
22 | Noise | Must test | E6 | |
23 | Illumination | Must test | E7 | |
24 | Microvibration | If necessary, measure | G2~4 | |
25 | Surface static electricity | If necessary, measure | E10 | |
26 | Surface static electricity | If necessary, measure | E9 | |
27 | Airflow pattern | Unexpected | If necessary, measure | E12.1 |
28 | Directional flow | Unexpected | If necessary, measure | E12.2 |
29 | Streamline parallelism | If necessary, measure | Unexpected | E12.3 |
30 | Self-cleaning time | If necessary, measure | E11 | |
31 | Molecular pollutants | If necessary, measure If necessary, measure | H2 | |
32 | Floating or settling bacteria | Clean rooms with microbial concentration parameter requirements must test E8.2~3 | E8.2~3 | |
33 | Surface contamination density | If necessary, measure | E8.4 | |
34 | Biological evaluation | If necessary, measure | F1~3 |
Requirements for the inspection time of mandatory items
Inspection items | Applicable level | Maximum inspection time interval |
Air supply volume | 6~9level | 12 months |
High efficiency filter scan for leak detection at air supply port | All Levels | 24 months |
High efficiency filter scan for leak detection at exhaust air | All Levels | 12 months |
Cross-sectional wind speed | 1~ 5level | 12 months |
Fresh air volume | All Levels | 12 months |
Exhaust air volume | All Levels | 12 months |
Static pressure difference | All Levels | 12 months |
Cleanliness at 0.6m inside the door | 1~5level | 12 months |
Air cleanliness | 1~5level | 24 months |
6~9level | 12 months | |
Formaldehyde concentration | All Levels | 24 months |
Temperature and humidity | All Levels | 12 months |
Noise | All Levels | 12 months |
Illumination | All Levels | 12 months |
Floating or settling bacteria | All Levels | 6 months |
Inspection items | Applicable level | Maximum inspection time interval |
Unevenness of wind speed | 1~4level | 12 months |
Wind speed at air outlet or specific boundary | 6~9level | 12 months |
Wind speed at tunnel outlet | All Levels | 12 months |
Temperature and humidity fluctuation range and regional differences | All Levels | 12 months or dynamic monitoring |
Micro-vibration | All Levels | 24 months |
Surface static electricity | All Levels | 24 months |
Airflow pattern | 6~9level | Unlimited |
Directional flow | 6~9level | 12 months |
Streamline parallelism | 1~5level | Unlimited |
Self-cleaning time | 5~9level | 24 months |
Enclosure tightness | On request | Unlimited |
Surface contamination density | All Levels | 6 months |
Biological evaluation | All Levels | Unlimited |
Molecular pollutants | 1~4level | 12 months |
Surface cleanliness | 1~5level | 12 months |
Ammonia concentration | All Levels | 24 months |
Ozone concentration | All Levels | Unlimited |
Carbon dioxide concentration | All Levels | 3 months |